5.2 TROUBLESHOOTING GUIDE FOR D-100 DISPLAY
NOTE: Also refer to the COMMISSIONING GUIDE located on the preceding pages.
Reported Problem Possible Solutions
Flow rate is indication zero ow.
(When uid is owing in the pipe.)
Verify that the correct supply voltage is
present at the ow meter power input.
Verify that the ow meter signal outputs
are properly wired to the display.
For insertion meters, verify that the
meter is correctly inserted and parallel
with the pipe.
For turbine meters, verify that the turbines
are not clogged with debris.
Re-conrm that there is really ow in the
pipe.
Displayed ow rate is too high or too low. Verify that the serial number of the ow
meter matches the serial number shown
on the label inside the D-100 front cover.
Verify that the correct supply voltage is
present at the ow meter power input.
Verify that the pipe diameter matches the
diameter shown on the calibration
certicate and on the ow meter tag.
For insertion meters, verify that the
meter is correctly inserted and parallel
with the pipe.
For turbine meters, verify that the turbines
are not clogged with debris.
Ai3 and/or Ai4 sensor values are too high or
too low.
Verify that the sensor scaling matches
that programmed values shown on the
label inside the D-100 front cover and on
the calibration certicate.
Conrm that the control system is
correctly scaled.
Data is not available at the control system. Verify network addresses are properly
programmed into the D-100.
If applicable, verify the Baud rate.
Check the polarity of the network
connections.