F-5100 Inline Thermal Mass Flow Meter Manual 05/15 - 0686-11 / 18332 Page 20
4.4 START-UP & COMMISSIONING
Please read the entire procedure before proceeding. A worksheet for checking off the following
steps and recording measured values is located on the next page.
1. Conrm ow meter location.
Conrm adequate straight pipe run
to achieve desired results.
Is the meter located in the correct location as required by the plans?
Compare actual straight pipe upstream and downstream of the me-
ter location to recommended distances identied in this manual.
2. Conrm orientation. Refer to the information in section 3.1 of this manual to ensure
that the meter is properly oriented with respect to the direction of
ow.
3. Conrm control system
programming.
Conrm that the control system input point is properly congured
for the analog range and/or scale factor identied on the calibration
tag
& certicate.
4. Conrm connection to
correct ONICON display
Conrm that the ow meter serial number matches the ONICON
display (when ordered together).
5. Verify wiring before connecting
power.
Prior to connecting the power, verify that the wiring is correct as
shown in this manual and/or on additional wiring diagrams pro-
vided with the ONICON display. If in doubt, contact ONICON for
assistance before proceeding further.
6. Conrm correct supply voltage. Verify that the supply voltage matches the voltage listed on the
meter tag.
7. Connect power. Wait approximately 45 seconds after power-on before proceeding
further.
The following steps require ow in the pipe. Flow signal readings should be taken while
holding the ow rate constant, if possible. Otherwise, take the various output readings as
quickly as possible.
8. Measure and record analog and
pulse outputs.
Current Output:
Scaled Output:
Refer to ow meter wiring diagram to locate the correct output
terminals. Use the following formula to calculate the ow rate from
the analog signal measurement:
SCFM = (measured current in mA - 4) X Full Scale Flow Rate
16
Each 24VDC pulse = unit volume identied as “Scale Factor” (mea-
sure and record time interval between pulses)
9. Compare output signals to each
other and to the ow rate displayed
by the control system.
Compare the ow rate calculated in step 8 to the ow rate indicated
by the control system. Conrm that the control system is registering
scaled output pulses as they occur.
Refer to troubleshooting guide when readings are inconsistent.