Onicon F-5200 Inline Bedienungsanleitung Seite 11

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 20
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 10
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5200 Inline Thermal Mass Flow Meter Manual 05/14 - 0763-4 / 19476 Page 11
ONICON Inline Thermal Mass Flow Meters are provided with either threaded of anged process
connections. Threaded meters are provided with male NPT threads and anged meters are
provided with ANSI class 150 or class 300 anges. Flow meters should be installed in accordance
with the requirements of section 3.1 INSTALLATION SITE SELECTION.
ONICON does not supply gaskets for anged meters.
3.2.1 Threaded Meter
FLOW DIRECTION
D
L
H
D
L
H
FLOW DIRECTION
Built-in flow conditioner
Output signal(s)
to control system
Optional
ONICON
Display
FLOW
FLOW DIRECTION
IMPORTANT NOTICE
Always use the maximum available straight run. When more than the minimum required straight
run is available place the meter such that the excess straight run is upstream of the meter location.
The ow meter must also be properly installed with respect to the direction of ow. Installing the
meter with the ow arrow pointing in the wrong direction will result in signicant errors in the
ow measurement.
i
3.2 MECHANICAL INSTALLATION
!
DO NOT LOOSEN
THESE FITTINGS
WARRANTY VOID
IF REMOVED
!
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • [email protected]
F-5200 Inline
Thermal Mass Flow Meter
Installation and Operation Guide
11-11
0763
WARNING