Onicon System-10 MODBUS Bedienungsanleitung Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 35
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-MOD Network Interface Installation Guide 05/14 - 0653-10 / 18321 Page 21
REGISTER
ADDRESS
DESCRIPTION
REG-
ISTER
TYPE
DATA
RANGE
OVER
RANGE
READ/
WRITE
COMMENT
41001
Meter Operating Mode
Indicator
Integer 1 – 3
Not
applicable
Read Only
1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode
41002 Mode Status Indicator Integer 1 – 2
Not
applicable
Read Only
1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction
REGISTER
ADDRESS
DESCRIPTION REGISTER TYPE
READ/
WRITE
COMMENT
41003 Energy Rate – Btu/Hr Floating point register (1 of 2) Read Only
41004 Energy Rate – Btu/Hr Floating point register (2 of 2) Read Only
41005 Energy Rate – kW Floating point register (1 of 2) Read Only
41006 Energy Rate – kW Floating point register (2 of 2) Read Only
41007 Energy Rate – Tons Floating point register (1 of 2) Read Only
41008 Energy Rate – Tons Floating point register (2 of 2) Read Only
41009 Volume Rate – GPM Floating point register (1 of 2) Read Only
41010 Volume Rate – GPM Floating point register (2 of 2) Read Only
41011 Volume Rate – GPH Floating point register (1 of 2) Read Only
41012 Volume Rate – GPH Floating point register (2 of 2) Read Only
41013 Volume Rate – MGD Floating point register (1 of 2) Read Only
41014 Volume Rate – MGD Floating point register (2 of 2) Read Only
41015 Volume Rate – L/S Floating point register (1 of 2) Read Only
41016 Volume Rate – L/S Floating point register (2 of 2) Read Only
41017 Volume Rate – L/M Floating point register (1 of 2) Read Only
41018 Volume Rate – L/M Floating point register (2 of 2) Read Only
41019 Volume Rate – L/H Floating point register (1 of 2) Read Only
41020 Volume Rate – L/H Floating point register (2 of 2) Read Only
41021 Volume Rate – M³/Hr Floating point register (1 of 2) Read Only
41022 Volume Rate – M³/Hr Floating point register (2 of 2) Read Only
41071 Volume Rate - Ft
3
/S Floating point register (1 of 2) Read Only
41072 Volume Rate - Ft
3
/S Floating point register (2 of 2) Read Only
41073 Volume Rate - Ft
3
/M Floating point register (1 of 2) Read Only
41074 Volume Rate - Ft
3
/M Floating point register (2 of 2) Read Only
41023 Mass Rate – Lb/Hr Floating point register (1 of 2) Read Only
Mass units are only
available when using
an F-2000 Series
Vortex meter
41024 Mass Rate – Lb/Hr Floating point register (2 of 2) Read Only
41025 Mass Rate – Kg/Hr Floating point register (1 of 2) Read Only
41026 Mass Rate – Kg/Hr Floating point register (2 of 2) Read Only