
1
1451 South Belcher Road, Largo, FL 33773 • USA
• T
el +1 (727) 447-6140 • Fax (727) 442-5699 •
[email protected]System-30 BTU Measurement System MODBUS RTU RS485 04/14 - 0583-1 / 18345 Page 14
It is often desirable to totalize the amount of energy transferred in each mode in separate registers.
For these applications, ONICON BTU meters may be congured for dual mode operation. In this
conguration, the meter will measure and totalize energy in separate registers based on the
polarity of the Delta t.
The drawings and tables below illustrate the relationship between meter location, temperature
sensor and mode of operation.
Temperature Sensor/ Mode of Operation Relationship with Meter in Supply Line
Supply Temp Temperature 1 Sensor (Internal Sensor)
Return Temp Temperature 2 Sensor (External Sensor)
Mode 1 Total Heating (Supply Temp > Return Temp)
Mode 2 Total Cooling (Supply Temp < Return Temp)
SYSTEM-30 BTU MEASUREMENT SYSTEM WITH INTEGRAL
FLOW METER & TEMPERATURE SENSORS
0333-2
INCORPORATED
ISOLATION VALVE
Normally Open
ISOLATION VALVE
Normally Open
BYPASS VALVE
Normally Closed
20"
5"
CHILLED WATER
SUPPLY
Y Strainer Upstream
Of Flow Meter
CHILLED WATER
RETURN
CONTROL SYSTEM
BACnet MS/TP
NETWORK
24 VAC POWER
FAN COIL UNIT
OR
AIR HANDLING UNIT
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
01-13-09
RETURN TEMP
FLOW
DIAGNOSTIC
LED’S
CONTROL SYSTEM
MODBUS RTU
NETWORK
24 VAC POWER
Kommentare zu diesen Handbüchern