System-40-BAC BTU Meter Manual 03/15 - 1045-2 Page 10
IMPORTANT NOTE
The ow sensor body must be correctly oriented with respect to the direction of ow in the pipe.
Meters installed with ow in the reverse direction will not function.
i
The calculator enclosure may be rotated around the axis of the ow sensor into three different
positions. To rotate, temporarily slide the enclosure off the ow sensor mounting brackets.
Remove the two retaining screws and reposition the mounting brackets as required. Reinstall
the enclosure with the display properly oriented for viewing. Mounting tracks on the back of
the enclosure allow for mounting in any orientation.
Flow Direction
The sensor port is always on
the downstream end of meter.
Retaining Nut SealCoupling
Slide calculator
enclosure to
remove from
sensor mounting
brackets
Slide Enclosure
Mounting Tracks
Retaining
Screw
Retaining
Screw
IMPORTANT NOTE
When installing the meter in a vertical pipe with upward ow you must rotate the enclosure back
plate 180° when rotating the display 90°. To accomplish this, temporarily remove the 4 cover
screws and rotate the backing plate.
i
The ow sensor is installed with threaded meter couplings and at sealing gaskets as shown
below. Orient the sensor body by aligning the ow direction arrow with the direction of ow
in the pipe.