F-3100 Flow Meter Manual 06/14 - 0670-7 Page 28
0516
Remove retaining screw to
expose connector.
(Shown with High Voltage)
Power connections
are under this cover.
Pulse Out 1
Pin 16 - Pos (+)
Pin 17 - Neg (-)
Pulse Out 2
Pin 18 - Pos (+)
Pin 19 - Neg (-)
4-20 mA Output
Pin 9 - Pos (+)
Pin 10 - Neg (-)
5-15-08
SIGNAL CONNECTIONS
POWER CONNECTIONS
Step 1: Loosen screws to lift cover. Step 2: Lift cover to expose electrical connections.
Step 3: Make SIGNAL connections as shown
Pull straight out on connectors to remove them.
Step 4: Open cover to expose POWER Connections.
Opto-coupled open collector pulse outputs
Maximum voltage: 40VDC
Maximum current: 100mA
Maximum saturation voltage collector/emitter @ 100mA: 3 VDC
Pulse Output 1 / Pulse Output 2
Seitenansicht 27