Seitenansicht 6
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-3100 Flow Meter Manual 06/14 - 0670-7 Page 7
SECTION 1.0: INTRODUCTION
1.1 PURPOSE OF THIS GUIDE
The purpose of this guide is to provide installation and commissioning procedures and basic
operating instructions for the F-3100 Inline Electromagnetic Flow Meter.
1.2 PRINCIPLE OF OPERATION
The operating principles of ONICON F-3100 Inline Electromagnetic Flow Meters are based
on Faraday’s Law of Electromagnetic Induction. Faraday’s Law states that a voltage will be
induced in a conductor (water or other conductive liquid) when it passes through a magnetic eld
(generated by the meter), and the induced voltage will be directly proportional to the velocity of
the conductor. By placing electrodes on opposite sides of the ow tube, it is possible to accurately
measure the induced voltage and determine the corresponding velocity of the owing liquid.
1.3 TYPICAL FLOW METER INSTALLATION
ONICON’S F-3100 Series Inline Magnetic Flow Meters are suitable for volumetric ow
measurement of electrically conductive liquids in a wide variety of applications including
bi-directional applications.
WARNING
Only qualied service personnel should attempt to install or service this product. Serious injury
may result from the improper installation or use of this product.
!
Flow direction
INSTALLATION IN STEEL (CONDUCTIVE) PIPE
F-3000 Series Mating Flange Grounding Kit Instructions
Note 1.
Using a #21 (0.159”) drill bit, drill a ½” deep hole in edge of each mating flange. Tap each hole using a 10-32 tap.
Secure the provided ring connectors and grounding wires to the flanges using the provided green grounding screws.
(Alternate method: Weld 10-32 studs (not provided) to the flange faces and attach ring connectors with 10-32 nuts (not provided.)
Note 2.
Provide a ground connection at the input power terminals inside the transmitter enclosure.
Note 3.
Provide a quality earth ground connection to the meter.
From best to worst, grounding options include:
1. Earth grounding rod driven into the soil.
2. Earth wire connected directly to the building electrical service panel.
3. Earth wire connection inside an electrical outlet near the meter.