P1 POINTS
Pt Name/Range Type Category COV OVR Default Initial Current
1 Address Range: 1-99 02 LAO NO YES 99 11
H
None
2 Application 02 LAO NO NO 1999
10
1999
10
None
3 Energy Rate - 0-32,767 03 LAI YES NO 0 0 Integer
4 Flow Rate - 0-32,767 03 LAI YES NO 0 0 Integer
5 Supply Temperature - 0-250°F 03 LAI YES NO 0 0 Integer
6 Return Temperature - 0-250°F 03 LAI YES NO 0 0 Integer
7 Delta Temperature - 0-250°F 03 LAI YES NO 0 0 Integer
8 Operating Mode: 1/Heat, 2/Cool 03 LDI NO NO 0 0 Byte
9 W0-M1 Energy: 000,000-009,999 03 LAI NO NO 0 0 Integer
10 W1-M1 Energy: 010,000-999,999 03 LAI NO NO 0 0 Integer
11 W0-M1Volume: 000,000-009,999 03 LAI NO NO 0 0 Integer
12 W1-M1 Volume: 010,000-999,999 03 LAI NO NO 0 0 Integer
13 W0-M2 Energy: 000,000-009,999 03 LAI NO NO 0 0 Integer
14 W1-M2 Energy: 010,000-999,999 03 LAI NO NO 0 0 Integer
15 W0-M2 Volume: 000,000-009,999 03 LAI NO NO 0 0 Integer
16 W1-M2 Volume: 010,000-999,999 03 LAI NO NO 0 0 Integer
17 W0-AuxiIn-1: 000,000-009,999 (Di3) 03 LAI NO NO 0 0 Integer
18 W1-AuxiIn-2: 010,000-999,999 (Di3) 03 LAI NO NO 0 0 Integer
19 Not Used
20 Point 20, Override Time (Hours)
Range 0-FF
02 LAO NO YES 1 1 None
21 M-1 E Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
22 M-1 V Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
23 M-2 E Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
24 M-2 V Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
25 AuxIn Reset - 0/Off, 1/Reset (Di3) 01 LDO NO YES 0 0 Byte
29 DAY.NGT
ON=Night; OFF=Day; Default=OFF
01 LDO NO YES 0 0 Byte
99 ERROR STATUS Bit Oriented 01 LAO NO YES 0 0 Integer
100 Point 100
Factory Flag
Factory Flag is not a point in the sense that the others are. It is referenced only by
the Memorize Point Command. Other commands should NAK it with “POINT DOES
NOT EXIST”.
NOTE: Also refer to the Siemens’ Application Note, Document No. 140-0280 for additional information.