11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5200 Insertion Thermal Mass Flow Meter Manual 05/14 - 0756-8 / 19475 Page 14
INSTALLATION KIT COMPONENTS
¾” WELD-ON ¾” CLOSE ¾” FULL PORT ¾” CLOSE ½” COMPRESSION WELDMENT WITH
BRANCH OUTLET NIPPLE BALL VALVE NIPPLE FITTING CABLE & COLLARS
5/8” MINIMUM DIA
ACCESS HOLE
3.2.2 Directions For Standard Installation (During New Construction)
1. Identify an appropriate location for the ow meter.
2. Weld the branch outlet onto the pipe.
3. Drill a 5/8 inch (minimum) access hole, centered in the branch outlet.
4. Install the close nipple, ball valve, reducer bushing (or close nipple and
weldment) and compression tting as shown above; use a paste type thread
sealant or Teon® tape as needed.
5. Flush and pressurize the system.
3.2.3 Directions For Hot Tap Installation (A Pressurized System)
1. Identify an appropriate location for the ow meter.
2. Weld the branch outlet onto the pipe.
3. Install the close nipple and ball valve as shown below; use a paste type thread
sealant or use Teon® tape.
4. Use a hot tap drilling machine to create the 5/8” access hole.
5. Remove the drill and clear all debris from the valve.
6. Install the reducer bushing and compression tting (or weldment and
compression tting) using paste type thread sealant or Teon tape as needed.
50 PSIG Maximum Pressure
500 PSIG Maximum Pressure
G
G
L
L
¾” NPT BRANCH ¾” CLOSE ¾” FULL PORT ¾” TO ½” REDUCER ½” COMPRESSION
OUTLET NIPPLE BALL VALVE BUSHING FITTING
INSTALLATION KIT COMPONENTS
MINIMUM DIA
ACCESS HOLE
(Exploded view)
Compression
Fitting