INSTALLATION KIT COMPONENTS
¾” WELD-ON ¾” CLOSE ¾” FULL PORT ¾” CLOSE ½” COMPRESSION WELDMENT WITH
BRANCH OUTLET NIPPLE BALL VALVE NIPPLE FITTING CABLE & COLLARS
5/8” MINIMUM DIA
ACCESS HOLE
3.2.2 Directions For Standard Installation (During New Construction)
1. Identify an appropriate location for the ow meter.
2. Weld the branch outlet onto the pipe.
3. Drill a 5/8 inch (minimum) access hole, centered in the branch outlet.
4. Install the close nipple, ball valve, reducer bushing (or close nipple and
weldment) and compression tting as shown above; use a paste type thread
sealant or Teon® tape as needed.
5. Flush and pressurize the system.
3.2.3 Directions For Hot Tap Installation (A Pressurized System)
1. Identify an appropriate location for the ow meter.
2. Weld the branch outlet onto the pipe.
3. Install the close nipple and ball valve as shown below; use a paste type thread
sealant or use Teon® tape.
4. Use a hot tap drilling machine to create the 5/8” access hole.
5. Remove the drill and clear all debris from the valve.
6. Install the reducer bushing and compression tting (or weldment and
compression tting) using paste type thread sealant or Teon tape as needed.
50 PSIG Maximum Pressure
500 PSIG Maximum Pressure
¾” NPT BRANCH ¾” CLOSE ¾” FULL PORT ¾” TO ½” REDUCER ½” COMPRESSION
OUTLET NIPPLE BALL VALVE BUSHING FITTING
INSTALLATION KIT COMPONENTS
⅝” MINIMUM DIA
ACCESS HOLE
(Exploded view)
Compression
Fitting