F-5200 Insertion Thermal Mass Flow Meter Manual 05/14 - 0756-8 / 19475 Page 20
3.5.2 Analog Output
The F-5200 is provided with a single 4-20 mA output for instantaneous rate.
Active Output Conguration (Default)
The default conguration for this output is as an active 4-20mA output. In this conguration the
output is electrically isolated from earth, but is common with input power. The blue wire is the
active (+) 4-20mA signal and the brown wire is the (-) 4-20mA return.
Loop Powered Conguration
(Only the output is loop powered, the meter still requires power.)
By changing the position of switch S1 located inside the enclosure, it is possible to loop power
the 4-20mA output. In this conguration the output is electrically isolated from earth and from
input power. In this conguration, an external DC voltage (+) VDC (12 – 24 VDC) is applied to the
yellow wire and the blue wire is the (+) 4-20mA signal. The brown (-) 4-20mA return wire is not
used.
The 4-20mA output is programmed at the factory. Refer to the attached laminated tag or the
certicate of calibration for information regarding the programmed full scale ow.
Contact ONICON for assistance if the full scale ow rate requires reprogramming.
3.5.3 Pulse Output
The F-5200 is provided with a single scaled pulse output for totalizing. This is an isolated dry
contact output. Maximum contact ratings are 50VDC @ 100mA. Pulse duration is 500ms.
This output is programmed at the factory. Refer to the attached laminated tag or the certicate of
calibration for information regarding the programmed pulse value.
Contact ONICON for assistance if the scaled pulse output requires reprogramming.